EasyManua.ls Logo

Siemens SIPROTEC 4 - Page 202

Siemens SIPROTEC 4
734 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
fore suitable for ground fault direction in resonant grounded systems where quantity 3Ι0 · cos ϕ is relevant.
The directional limit lines are perpendicular to axis 3Ι0
real
.
[7sj6-richtungskennlinie-bei-cos-messung-101210, 1, en_US]
Figure 2-82 Directional characteristic for cos–ϕ–measurement
The directional limit lines may be rotated by a correction angle (address PHI CORRECTION) up to ± 45°.
Therefore, in grounded systems it is possible e.g. to increase sensitivity in the resistive-inductive range with a
rotation of –45°, or in case of electric machines connected to the busbar of an ungrounded power system in
the resistive- capacitive range with a rotation of +45° (see the following Figure). Furthermore the directional
limit lines may be rotated by 90° to determine ground faults and their direction in isolated systems.
[richtungskennlinien-260602-kn, 1, en_US]
Figure 2-83 Directional characteristic for cos–ϕ–measurement
Functions
2.13 Ground Fault Protection 64, 67N(s), 50N(s), 51N(s)
202 SIPROTEC 4, 7SJ62/64, Manual
C53000-G1140-C207-8, Edition 08.2016

Table of Contents

Other manuals for Siemens SIPROTEC 4

Related product manuals