Addr. Parameter Setting Options Default Setting Comments
7166 50-3 No influence
Starts 79
Stops 79
No influence 50-3
7167 50N-3 No influence
Starts 79
Stops 79
No influence 50N-3
7168 67-3 No influence
Starts 79
Stops 79
No influence 67-3
7169 67N-3 No influence
Starts 79
Stops 79
No influence 67N-3
7172 67Ns-1 No influence
Starts 79
Stops 79
No influence 67Ns-1
7173 67Ns-2 No influence
Starts 79
Stops 79
No influence 67Ns-2
7174 67Ns TOC No influence
Starts 79
Stops 79
No influence 67Ns TOC
7175 bef.1.Cy:67Ns-1 Set value T=T
instant. T=0
blocked T=∞
Set value T=T before 1. Cycle: 67Ns-1
7176 bef.1.Cy:67Ns-2 Set value T=T
instant. T=0
blocked T=∞
Set value T=T before 1. Cycle: 67Ns-2
7177 bef.1Cy:67NsTOC Set value T=T
instant. T=0
blocked T=∞
Set value T=T before 1. Cycle: 67Ns TOC
7178 bef.2.Cy:67Ns-1 Set value T=T
instant. T=0
blocked T=∞
Set value T=T before 2. Cycle: 67Ns-1
7179 bef.2.Cy:67Ns-2 Set value T=T
instant. T=0
blocked T=∞
Set value T=T before 2. Cycle: 67Ns-2
7180 bef.2Cy:67NsTOC Set value T=T
instant. T=0
blocked T=∞
Set value T=T before 2. Cycle: 67Ns TOC
7181 bef.3.Cy:67Ns-1 Set value T=T
instant. T=0
blocked T=∞
Set value T=T before 3. Cycle: 67Ns-1
7182 bef.3.Cy:67Ns-2 Set value T=T
instant. T=0
blocked T=∞
Set value T=T before 3. Cycle: 67Ns-2
7183 bef.3Cy:67NsTOC Set value T=T
instant. T=0
blocked T=∞
Set value T=T before 3. Cycle: 67Ns TOC
Functions
2.16 Automatic Reclosing System 79
SIPROTEC 4, 7SJ62/64, Manual 253
C53000-G1140-C207-8, Edition 08.2016