Motor Restart Inhibit 66, 86
Approximate computation of the rotor overtemperature
Startup is permitted only if the rotor has sufficient thermal reserves for a complete startup
Disabling of the start inhibit is possible if an emergency startup is required.
Load Jam Protection for Motors 51M
Protection of motors during sudden rotor blocking
Evaluation of the positive sequence system of phase currents
Evaluation of the circuit breaker switching state
Blocking of function during motor standstill and during motor startup
Frequency Protection 81 O/U
Monitoring of falling below (f<) and/or exceeding (f>) with 4 frequency limits and time delays that are
independently adjustable
Insensitive to harmonics and abrupt phase angle changes
Adjustable undervoltage threshold.
Undervoltage-controlled reactive power protection (27/Q)
Detection of critical power system situations
Disconnection of power supply facilities from the grid
Reconnection under stable power system conditions
Thermal Overload Protection 49
Thermal profile of energy losses (overload protection has full memory capability)
True r.m.s. calculation
Adjustable thermal warning element
Adjustable alarm level based on current magnitude
Additional time constant setting for motors to accommodate the motor at standstill
Integration of ambient temperature or coolant temperature is possible via external temperature sensors
and RTD-Box.
Monitoring Functions
Reliability of the device is greatly increased because of self-monitoring of the internal measurement
circuits, the auxiliary power supply as well as the hardware and software
Monitoring of the current transformer and voltage transformer secondary circuits using summation and
symmetry check techniques
Trip circuit monitoring possible
Phase rotation check.
Ground Fault Detection 50N(s), 51N(s), 67N(s), 59N/64
Displacement voltage is measured or calculated from the three phase voltages
Determination of a faulty phase on ungrounded or grounded systems
Two-element Ground Fault Detection: 50Ns-1 and 50Ns-2
High sensitivity (as low as 1 mA)
Introduction
1.3 Characteristics
SIPROTEC 4, 7SJ62/64, Manual 27
C53000-G1140-C207-8, Edition 08.2016

Table of Contents

Other manuals for Siemens SIPROTEC 4

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 4 and is the answer not in the manual?

Siemens SIPROTEC 4 Specifications

General IconGeneral
BrandSiemens
ModelSIPROTEC 4
CategoryProtection Device
LanguageEnglish

Related product manuals