Binary inputs Jumper
DC 19 V threshold
1)
DC 88 V threshold
3)
DC 176 V threshold
3)
BI36 X23 1-2 2-3 3-4
BI37 X24 1-2 2-3 3-4
BI38 X25 1-2 2-3 3-4
BI39 X26 1-2 2-3 3-4
BI40 X27 1-2 2-3 3-4
BI41 X28 1-2 2-3 3-4
BI42 X29 1-2 2-3 3-4
BI43 X30 1-2 2-3 3-4
BI44 X31 1-2 2-3 3-4
BI45 X32 1-2 2-3 3-4
BI46 X33 1-2 2-3 3-4
BI47 X34 1-2 2-3 3-4
BI48 X35 1-2 2-3 3-4
1)
Factory settings for devices with power supply voltages of DC 24 V to 125 V
2)
Factory settings for devices with power supply voltages of DC 110 V to 250 V and AC 115 V/ 230 V
3)
Use only with control voltages DC 220 V or 250 V
Bus Address
Jumpers X71, X72 and X73 on the C–I/O-4 board serve to set the bus address. The jumpers must not be
changed. The following table lists the jumper presettings.
Table 3-28
Jumper Settings of Bus Addresses of the input/output board C-I/O-4
Jumper Presetting
X71 1-2 (H)
X72 1-2 (H)
X73 1-2 (H)
Mounting and Commissioning
3.1 Mounting and Connections
SIPROTEC 4, 7SJ62/64, Manual 399
C53000-G1140-C207-8, Edition 08.2016