Addr. Parameter Function C Setting Options Default Setting Comments
2101 67Nc-2 PICKUP ColdLoadPickup 1A 0.05 .. 35.00 A; ∞ 7.00 A 67Nc-2 Pickup
5A 0.25 .. 175.00 A; ∞ 35.00 A
2102 67Nc-2 DELAY ColdLoadPickup 0.00 .. 60.00 sec; ∞ 0.00 sec 67Nc-2 Time Delay
2103 67Nc-1 PICKUP ColdLoadPickup 1A 0.05 .. 35.00 A; ∞ 1.50 A 67Nc-1 Pickup
5A 0.25 .. 175.00 A; ∞ 7.50 A
2104 67Nc-1 DELAY ColdLoadPickup 0.00 .. 60.00 sec; ∞ 0.30 sec 67Nc-1 Time Delay
2105 67Nc-TOC PICKUP ColdLoadPickup 1A 0.05 .. 4.00 A 1.00 A 67Nc-TOC Pickup
5A 0.25 .. 20.00 A 5.00 A
2106 67Nc-TOC T-DIAL ColdLoadPickup 0.05 .. 3.20 sec; ∞ 0.50 sec 67Nc-TOC Time Dial
2107 67Nc-TOC T-DIAL ColdLoadPickup 0.50 .. 15.00 ; ∞ 5.00 67Nc-TOC Time Dial
2108 67Nc-3 PICKUP ColdLoadPickup 0.25 .. 35.00 A; ∞ ∞ A 67Nc-3 Pickup
2109 67Nc-3 DELAY ColdLoadPickup 0.00 .. 60.00 sec; ∞ 0.00 sec 67Nc-3 Time Delay
2201 INRUSH REST. 50/51 Overcur. OFF
ON
OFF Inrush Restraint
2202 2nd HARMONIC 50/51 Overcur. 10 .. 45 % 15 % 2nd. harmonic in % of
fundamental
2203 CROSS BLOCK 50/51 Overcur. NO
YES
NO Cross Block
2204 CROSS BLK TIMER 50/51 Overcur. 0.00 .. 180.00 sec 0.00 sec Cross Block Time
2205 I Max 50/51 Overcur. 1A 0.30 .. 25.00 A 7.50 A Maximum Current for
Inrush Restraint
5A 1.50 .. 125.00 A 37.50 A
2701 50 1Ph 50 1Ph OFF
ON
OFF 50 1Ph
2702 50 1Ph-2 PICKUP 50 1Ph 1A 0.05 .. 35.00 A; ∞ 0.50 A 50 1Ph-2 Pickup
5A 0.25 .. 175.00 A; ∞ 2.50 A
2703 50 1Ph-2 PICKUP 50 1Ph 0.003 .. 1.500 A; ∞ 0.300 A 50 1Ph-2 Pickup
2704 50 1Ph-2 DELAY 50 1Ph 0.00 .. 60.00 sec; ∞ 0.10 sec 50 1Ph-2 Time Delay
2705 50 1Ph-1 PICKUP 50 1Ph 1A 0.05 .. 35.00 A; ∞ 0.20 A 50 1Ph-1 Pickup
5A 0.25 .. 175.00 A; ∞ 1.00 A
2706 50 1Ph-1 PICKUP 50 1Ph 0.003 .. 1.500 A; ∞ 0.100 A 50 1Ph-1 Pickup
2707 50 1Ph-1 DELAY 50 1Ph 0.00 .. 60.00 sec; ∞ 0.50 sec 50 1Ph-1 Time Delay
3101 Sens. Gnd Fault Sens. Gnd Fault OFF
ON
ON with GF log
Alarm Only
OFF (Sensitive) Ground Fault
3102 CT Err. I1 Sens. Gnd Fault 0.001 .. 1.600 A 0.050 A Current I1 for CT Angle
Error
3102 CT Err. I1 Sens. Gnd Fault 1A 0.05 .. 35.00 A 1.00 A Current I1 for CT Angle
Error
5A 0.25 .. 175.00 A 5.00 A
3103 CT Err. F1 Sens. Gnd Fault 0.0 .. 5.0 ° 0.0 ° CT Angle Error at I1
3104 CT Err. I2 Sens. Gnd Fault 0.001 .. 1.600 A 1.000 A Current I2 for CT Angle
Error
3104 CT Err. I2 Sens. Gnd Fault 1A 0.05 .. 35.00 A 10.00 A Current I2 for CT Angle
Error
5A 0.25 .. 175.00 A 50.00 A
3105 CT Err. F2 Sens. Gnd Fault 0.0 .. 5.0 ° 0.0 ° CT Angle Error at I2
3106 VPH MIN Sens. Gnd Fault 10 .. 100 V 40 V L-Gnd Voltage of Faulted
Phase Vph Min
Functions, Settings, Information
F.2 Settings
628 SIPROTEC 4, 7SJ62/64, Manual