Addr. Parameter Function C Setting Options Default Setting Comments
6140 SYNC PERMIS. SYNC function
1
YES
NO
YES Switching at synchronous
conditions
6141 F SYNCHRON SYNC function
1
0.01 .. 0.04 Hz 0.01 Hz Frequency threshold
ASYN <--> SYN
6142 dV SYNC V2>V1 SYNC function
1
0.5 .. 50.0 V 5.0 V Maximum voltage differ-
ence V2>V1
6143 dV SYNC V2<V1 SYNC function
1
0.5 .. 50.0 V 5.0 V Maximum voltage differ-
ence V2<V1
6144 dα SYNC α2> α1 SYNC function
1
2 .. 80 ° 10 ° Maximum angle differ-
ence alpha2>alpha1
6145 dα SYNC α2< α1 SYNC function
1
2 .. 80 ° 10 ° Maximum angle differ-
ence alpha2<alpha1
6146 T SYNC-DELAY SYNC function
1
0.00 .. 60.00 sec 0.00 sec Release delay at synchro-
nous conditions
6150 dV SYNCHK V2>V1 SYNC function
1
0.5 .. 50.0 V 5.0 V Maximum voltage differ-
ence V2>V1
6151 dV SYNCHK V2<V1 SYNC function
1
0.5 .. 50.0 V 5.0 V Maximum voltage differ-
ence V2<V1
6152 df SYNCHK f2>f1 SYNC function
1
0.01 .. 2.00 Hz 0.10 Hz Maximum frequency
difference f2>f1
6153 df SYNCHK f2<f1 SYNC function
1
0.01 .. 2.00 Hz 0.10 Hz Maximum frequency
difference f2<f1
6154 dα SYNCHK α2>α1 SYNC function
1
2 .. 80 ° 10 ° Maximum angle differ-
ence alpha2>alpha1
6155 dα SYNCHK α2<α1 SYNC function
1
2 .. 80 ° 10 ° Maximum angle differ-
ence alpha2<alpha1
6201 Synchronizing SYNC function
2
ON
OFF
OFF Synchronizing Function
6202 SyncCB SYNC function
2
(Einstellmöglich-
keiten anwendung-
sabhängig)
none Synchronizable circuit
breaker
6203 Vmin SYNC function
2
20 .. 125 V 90 V Minimum voltage limit:
Vmin
6204 Vmax SYNC function
2
20 .. 140 V 110 V Maximum voltage limit:
Vmax
6205 V< SYNC function
2
1 .. 60 V 5 V Threshold V1, V2 without
voltage
6206 V> SYNC function
2
20 .. 140 V 80 V Threshold V1, V2 with
voltage
6207 SYNC V1<V2> SYNC function
2
YES
NO
NO ON-Command at V1< and
V2>
6208 SYNC V1>V2< SYNC function
2
YES
NO
NO ON-Command at V1> and
V2<
6209 SYNC V1<V2< SYNC function
2
YES
NO
NO ON-Command at V1< and
V2<
6210A Direct CO SYNC function
2
YES
NO
NO Direct ON-Command
6211A TSUP VOLTAGE SYNC function
2
0.00 .. 60.00 sec 0.10 sec Supervision time of
V1>;V2> or V1<;V2<
6212 T-SYN. DURATION SYNC function
2
0.01 .. 1200.00 sec;
30.00 sec Maximum duration of
Synchronization
Functions, Settings, Information
F.2 Settings
638 SIPROTEC 4, 7SJ62/64, Manual
C53000-G1140-C207-8, Edition 08.2016

Table of Contents