Addr. Parameter Function C Setting Options Default Setting Comments
7164 BINARY INPUT 79M Auto Recl. No influence
Starts 79
Stops 79
No influence Binary Input
7165 3Pol.PICKUP BLK 79M Auto Recl. YES
NO
NO 3 Pole Pickup blocks 79
7166 50-3 79M Auto Recl. No influence
Starts 79
Stops 79
No influence 50-3
7167 50N-3 79M Auto Recl. No influence
Starts 79
Stops 79
No influence 50N-3
7168 67-3 79M Auto Recl. No influence
Starts 79
Stops 79
No influence 67-3
7169 67N-3 79M Auto Recl. No influence
Starts 79
Stops 79
No influence 67N-3
7172 67Ns-1 79M Auto Recl. No influence
Starts 79
Stops 79
No influence 67Ns-1
7173 67Ns-2 79M Auto Recl. No influence
Starts 79
Stops 79
No influence 67Ns-2
7174 67Ns TOC 79M Auto Recl. No influence
Starts 79
Stops 79
No influence 67Ns TOC
7175 bef.1.Cy:67Ns-1 79M Auto Recl. Set value T=T
instant. T=0
blocked T=∞
Set value T=T before 1. Cycle: 67Ns-1
7176 bef.1.Cy:67Ns-2 79M Auto Recl. Set value T=T
instant. T=0
blocked T=∞
Set value T=T before 1. Cycle: 67Ns-2
7177 bef.1Cy:67NsTOC 79M Auto Recl. Set value T=T
instant. T=0
blocked T=∞
Set value T=T before 1. Cycle: 67Ns TOC
7178 bef.2.Cy:67Ns-1 79M Auto Recl. Set value T=T
instant. T=0
blocked T=∞
Set value T=T before 2. Cycle: 67Ns-1
7179 bef.2.Cy:67Ns-2 79M Auto Recl. Set value T=T
instant. T=0
blocked T=∞
Set value T=T before 2. Cycle: 67Ns-2
7180 bef.2Cy:67NsTOC 79M Auto Recl. Set value T=T
instant. T=0
blocked T=∞
Set value T=T before 2. Cycle: 67Ns TOC
7181 bef.3.Cy:67Ns-1 79M Auto Recl. Set value T=T
instant. T=0
blocked T=∞
Set value T=T before 3. Cycle: 67Ns-1
Functions, Settings, Information
F.2 Settings
SIPROTEC 4, 7SJ62/64, Manual 645
C53000-G1140-C207-8, Edition 08.2016