Addr. Parameter Function C Setting Options Default Setting Comments
7259 bef.2.Cy:67N-3 79M Auto Recl. Set value T=T
instant. T=0
blocked T=∞
Set value T=T before 2. Cycle: IE>>>
directional
7260 bef.3.Cy:67-3 79M Auto Recl. Set value T=T
instant. T=0
blocked T=∞
Set value T=T before 3. Cycle: 67-3
7261 bef.3.Cy:67N-3 79M Auto Recl. Set value T=T
instant. T=0
blocked T=∞
Set value T=T before 3. Cycle: IE>>>
directional
7262 bef.4.Cy:67-3 79M Auto Recl. Set value T=T
instant. T=0
blocked T=∞
Set value T=T before 4. Cycle: 67-3
7263 bef.4.Cy:67N-3 79M Auto Recl. Set value T=T
instant. T=0
blocked T=∞
Set value T=T before 4. Cycle: 67N-3
8001 START Fault Locator Pickup
TRIP
Pickup Start fault locator with
8101 MEASURE. SUPERV Meas-
urem.Superv
OFF
ON
ON Measurement Supervision
8102 BALANCE V-LIMIT Meas-
urem.Superv
10 .. 100 V 50 V Voltage Threshold for
Balance Monitoring
8103 BAL. FACTOR V Meas-
urem.Superv
0.58 .. 0.90 0.75 Balance Factor for
Voltage Monitor
8104 BALANCE I LIMIT Meas-
urem.Superv
1A 0.10 .. 1.00 A 0.50 A Current Threshold for
Balance Monitoring
5A 0.50 .. 5.00 A 2.50 A
8105 BAL. FACTOR I Meas-
urem.Superv
0.10 .. 0.90 0.50 Balance Factor for Current
Monitor
8106 Σ I THRESHOLD Meas-
urem.Superv
1A 0.05 .. 2.00 A; ∞ 0.10 A Summated Current Moni-
toring Threshold
5A 0.25 .. 10.00 A; ∞ 0.50 A
8107 Σ I FACTOR Meas-
urem.Superv
0.00 .. 0.95 0.10 Summated Current Moni-
toring Factor
8109 FAST Σ i MONIT Meas-
urem.Superv
OFF
ON
ON Fast Summated Current
Monitoring
8110A T BAL. V LIMIT Meas-
urem.Superv
0 .. 100 sec 5 sec T Balance Factor for
Voltage Monitor
8111A T BAL. I LIMIT Meas-
urem.Superv
0 .. 100 sec 5 sec T Current Balance
Monitor
8201 FCT 74TC 74TC TripCirc. ON
OFF
ON 74TC TRIP Circuit Supervi-
sion
8202 Alarm Delay 74TC TripCirc. 1 .. 30 sec 2 sec Delay Time for alarm
8301 DMD Interval Demand meter 15 Min., 1 Sub
15 Min., 3 Subs
15 Min.,15 Subs
30 Min., 1 Sub
60 Min., 1 Sub
60 Min.,10 Subs
5 Min., 5 Subs
60 Min., 1 Sub Demand Calculation Inter-
vals
Functions, Settings, Information
F.2 Settings
650 SIPROTEC 4, 7SJ62/64, Manual
C53000-G1140-C207-8, Edition 08.2016