Addr. Parameter Function C Setting Options Default Setting Comments
9056 RTD 5 STAGE 2 RTD-Box -58 .. 482 °F; ∞ 248 °F RTD 5: Temperature Stage
2 Pickup
9061A RTD 6 TYPE RTD-Box Not connected
Pt 100 Ω
Ni 120 Ω
Ni 100 Ω
Not connected RTD 6: Type
9062A RTD 6 LOCATION RTD-Box Oil
Ambient
Winding
Bearing
Other
Other RTD 6: Location
9063 RTD 6 STAGE 1 RTD-Box -50 .. 250 °C; ∞ 100 °C RTD 6: Temperature Stage
1 Pickup
9064 RTD 6 STAGE 1 RTD-Box -58 .. 482 °F; ∞ 212 °F RTD 6: Temperature Stage
1 Pickup
9065 RTD 6 STAGE 2 RTD-Box -50 .. 250 °C; ∞ 120 °C RTD 6: Temperature Stage
2 Pickup
9066 RTD 6 STAGE 2 RTD-Box -58 .. 482 °F; ∞ 248 °F RTD 6: Temperature Stage
2 Pickup
9071A RTD 7 TYPE RTD-Box Not connected
Pt 100 Ω
Ni 120 Ω
Ni 100 Ω
Not connected RTD 7: Type
9072A RTD 7 LOCATION RTD-Box Oil
Ambient
Winding
Bearing
Other
Other RTD 7: Location
9073 RTD 7 STAGE 1 RTD-Box -50 .. 250 °C; ∞ 100 °C RTD 7: Temperature Stage
1 Pickup
9074 RTD 7 STAGE 1 RTD-Box -58 .. 482 °F; ∞ 212 °F RTD 7: Temperature Stage
1 Pickup
9075 RTD 7 STAGE 2 RTD-Box -50 .. 250 °C; ∞ 120 °C RTD 7: Temperature Stage
2 Pickup
9076 RTD 7 STAGE 2 RTD-Box -58 .. 482 °F; ∞ 248 °F RTD 7: Temperature Stage
2 Pickup
9081A RTD 8 TYPE RTD-Box Not connected
Pt 100 Ω
Ni 120 Ω
Ni 100 Ω
Not connected RTD 8: Type
9082A RTD 8 LOCATION RTD-Box Oil
Ambient
Winding
Bearing
Other
Other RTD 8: Location
9083 RTD 8 STAGE 1 RTD-Box -50 .. 250 °C; ∞ 100 °C RTD 8: Temperature Stage
1 Pickup
9084 RTD 8 STAGE 1 RTD-Box -58 .. 482 °F; ∞ 212 °F RTD 8: Temperature Stage
1 Pickup
Functions, Settings, Information
F.2 Settings
SIPROTEC 4, 7SJ62/64, Manual 653
C53000-G1140-C207-8, Edition 08.2016