Addr. Parameter Function C Setting Options Default Setting Comments
9114 RTD11 STAGE 1 RTD-Box -58 .. 482 °F; ∞ 212 °F RTD11: Temperature
Stage 1 Pickup
9115 RTD11 STAGE 2 RTD-Box -50 .. 250 °C; ∞ 120 °C RTD11: Temperature
Stage 2 Pickup
9116 RTD11 STAGE 2 RTD-Box -58 .. 482 °F; ∞ 248 °F RTD11: Temperature
Stage 2 Pickup
9121A RTD12 TYPE RTD-Box Not connected
Pt 100 Ω
Ni 120 Ω
Ni 100 Ω
Not connected RTD12: Type
9122A RTD12 LOCATION RTD-Box Oil
Ambient
Winding
Bearing
Other
Other RTD12: Location
9123 RTD12 STAGE 1 RTD-Box -50 .. 250 °C; ∞ 100 °C RTD12: Temperature
Stage 1 Pickup
9124 RTD12 STAGE 1 RTD-Box -58 .. 482 °F; ∞ 212 °F RTD12: Temperature
Stage 1 Pickup
9125 RTD12 STAGE 2 RTD-Box -50 .. 250 °C; ∞ 120 °C RTD12: Temperature
Stage 2 Pickup
9126 RTD12 STAGE 2 RTD-Box -58 .. 482 °F; ∞ 248 °F RTD12: Temperature
Stage 2 Pickup
Functions, Settings, Information
F.2 Settings
SIPROTEC 4, 7SJ62/64, Manual 655
C53000-G1140-C207-8, Edition 08.2016