No. Description Function Typ
e of
Info
rma
tion
Log Buffers Configurable in Matrix IEC 60870-5-103
Event Log ON/OFF
Trip (Fault) Log ON/OFF
Ground Fault Log ON/OFF
Marked in Oscill. Record
LED
Binary Input
Function Key
Relay
Chatter Suppression
Type
information number
Data Unit
General Interrogation
146 Error -5V (Error -5V) Device,
General
OUT On
Of
f
* * LED BO
147 Error Power Supply (Error
PwrSupply)
Device,
General
OUT On
Of
f
* * LED BO
160 Alarm Summary Event
(Alarm Sum Event)
Device,
General
OUT On
Of
f
* * LED BO 16
0
46 1 Yes
161 Failure: General Current
Supervision (Fail I
Superv.)
Meas-
urem.Super
v
OUT On
Of
f
* * LED BO 16
0
32 1 Yes
162 Failure: Current Summa-
tion (Failure Σ I)
Meas-
urem.Super
v
OUT On
Of
f
* * LED BO 13
5
18
2
1 Yes
163 Failure: Current Balance
(Fail I balance)
Meas-
urem.Super
v
OUT On
Of
f
* * LED BO 13
5
18
3
1 Yes
167 Failure: Voltage Balance
(Fail V balance)
Meas-
urem.Super
v
OUT On
Of
f
* * LED BO 13
5
18
6
1 Yes
169 VT Fuse Failure (alarm
>10s) (VT FuseFail>10s)
Meas-
urem.Super
v
OUT On
Of
f
* * LED BO 13
5
18
8
1 Yes
170 VT Fuse Failure (alarm
instantaneous) (VT Fuse-
Fail)
Meas-
urem.Super
v
OUT On
Of
f
* * LED BO
170.00
01
>25-group 1 activate
(>25-1 act)
SYNC func-
tion 1
SP On
Of
f
* LED BI
170.00
01
>25-group 2 activate
(>25-2 act)
SYNC func-
tion 2
SP On
Of
f
* LED BI
170.00
01
>25-group 3 activate
(>25-3 act)
SYNC func-
tion 3
SP On
Of
f
* LED BI
170.00
01
>25-group 4 activate
(>25-4 act)
SYNC func-
tion 4
SP On
Of
f
* LED BI
170.00
43
>25 Synchronization
request (>25 Sync req.)
SYNC func-
tion 1
SP On
Of
f
* LED BI
Functions, Settings, Information
F.3 Information List
662 SIPROTEC 4, 7SJ62/64, Manual
C53000-G1140-C207-8, Edition 08.2016