No. Description Function Typ
e of
Info
rma
tion
Log Buffers Configurable in Matrix IEC 60870-5-103
Event Log ON/OFF
Trip (Fault) Log ON/OFF
Ground Fault Log ON/OFF
Marked in Oscill. Record
LED
Binary Input
Function Key
Relay
Chatter Suppression
Type
information number
Data Unit
General Interrogation
501 Relay PICKUP (Relay
PICKUP)
P.System
Data 2
OUT ON m LED BO 15
0
15
1
2 Yes
502 Relay Drop Out (Relay
Drop Out)
Device,
General
SP * *
510 General CLOSE of relay
(Relay CLOSE)
Device,
General
SP * *
511 Relay GENERAL TRIP
command (Relay TRIP)
P.System
Data 2
OUT ON m LED BO 15
0
16
1
2 Yes
533 Primary fault current Ia (Ia
=)
P.System
Data 2
VI ON
OFF
15
0
17
7
4 No
534 Primary fault current Ib
(Ib =)
P.System
Data 2
VI ON
OFF
15
0
17
8
4 No
535 Primary fault current Ic (Ic
=)
P.System
Data 2
VI ON
OFF
15
0
17
9
4 No
545 Time from Pickup to drop
out (PU Time)
Device,
General
VI ON
OFF
546 Time from Pickup to TRIP
(TRIP Time)
Device,
General
VI ON
OFF
561 Manual close signal
detected
(Man.Clos.Detect)
P.System
Data 2
OUT On
Of
f
* * LED BO
916 Increment of active
energy (WpΔ=)
Energy -
917 Increment of reactive
energy (WqΔ=)
Energy -
1020 Counter of operating
hours (Op.Hours=)
Statistics VI
1021 Accumulation of inter-
rupted current Ph A (Σ Ia
=)
Statistics VI
1022 Accumulation of inter-
rupted current Ph B (Σ Ib
=)
Statistics VI
1023 Accumulation of inter-
rupted current Ph C (Σ Ic
=)
Statistics VI
1106 >Start Fault Locator
(>Start Flt. Loc)
Fault
Locator
SP On * * LED BI BO 15
1
6 1 Yes
1114 Flt Locator: primary
RESISTANCE (Rpri =)
Fault
Locator
VI ON
OFF
1115 Flt Locator: primary REAC-
TANCE (Xpri =)
Fault
Locator
VI ON
OFF
Functions, Settings, Information
F.3 Information List
SIPROTEC 4, 7SJ62/64, Manual 681
C53000-G1140-C207-8, Edition 08.2016