No. Description Function Typ
e of
Info
rma
tion
Log Buffers Configurable in Matrix IEC 60870-5-103
Event Log ON/OFF
Trip (Fault) Log ON/OFF
Ground Fault Log ON/OFF
Marked in Oscill. Record
LED
Binary Input
Function Key
Relay
Chatter Suppression
Type
information number
Data Unit
General Interrogation
2884 Zone sequence coordina-
tion switched ON (ZSC
ON)
79M Auto
Recl.
OUT On * * LED BO
2885 Zone sequence coordina-
tion switched OFF (ZSC
OFF)
79M Auto
Recl.
OUT On * * LED BO
2889 79 1st cycle zone exten-
sion release (79 1.CycZo-
neRel)
79M Auto
Recl.
OUT * * * LED BO
2890 79 2nd cycle zone exten-
sion release (79 2.CycZo-
neRel)
79M Auto
Recl.
OUT * * * LED BO
2891 79 3rd cycle zone exten-
sion release (79 3.CycZo-
neRel)
79M Auto
Recl.
OUT * * * LED BO
2892 79 4th cycle zone exten-
sion release (79 4.CycZo-
neRel)
79M Auto
Recl.
OUT * * * LED BO
2896 No. of 1st AR-cycle CLOSE
commands,3pole (79
#Close1./3p=)
Statistics VI
2898 No. of higher AR-cycle
CLOSE commands,3p (79
#Close2./3p=)
Statistics VI
2899 79: Close request to
Control Function (79
CloseRequest)
79M Auto
Recl.
OUT * On * LED BO
4601 >52-a contact (OPEN, if
bkr is open) (>52-a)
P.System
Data 2
SP On
Of
f
* * LED BI BO
4602 >52-b contact (OPEN, if
bkr is closed) (>52-b)
P.System
Data 2
SP On
Of
f
* * LED BI BO
4822 >BLOCK 66 Motor Startup
Counter (>BLOCK 66)
48/66
Motorprot
SP * * * LED BI BO
4823 >66 Mot.St.Cnt: Emer-
gency start (>66
emer.start)
48/66
Motorprot
SP On
Of
f
* * LED BI BO 16
8
51 1 Yes
4824 66 Motor Startup Counter
OFF (66 OFF)
48/66
Motorprot
OUT On
Of
f
* * LED BO 16
8
52 1 Yes
4825 66 Motor Startup Counter
BLOCKED (66 BLOCKED)
48/66
Motorprot
OUT On
Of
f
On
Off
* LED BO 16
8
53 1 Yes
Functions, Settings, Information
F.3 Information List
SIPROTEC 4, 7SJ62/64, Manual 695
C53000-G1140-C207-8, Edition 08.2016