[scfastsc-270213-01.tif, 1, en_US]
Figure 7-11 Parameter Setting in the Example of the Fast-Scan Recorder
Ensure the parameter Mode is activated.
Default setting (_:2731:1) Mode = on
When using the overlapping parameter Mode , the recorder is activated.
Parameter Value
Description
on
The recorder is activated.
off
The recorder is deactivated in different ways depending on the recorded type:
The fast-scan recorder and the slow-scan recorder are deactivated.
The continuous recorder and the trend recorder are deactivated, but continue to record time
jumps, modes on/off, as well as disconnection and recovery of supply voltage.
PQDif recordings are still generated, even though the continuous recorder and the trend
recorder are set to the mode off. It is recommended to delete the instance in case of long-
term non-use.
test
The recorder is activated for test purposes. In the test mode, the record is marked using the test
flag (true) (see the following figure).
i
i
NOTE
The test mode is not available for the continuous recorder and the trend recorder and applies only to the
fast-scan and slow-scan recorders.
[sctestfl-291012-01.tif, 1, en_US]
Figure 7-12 Fault Record with Activated Marking Test Record (Test Flag)
Fault Recorder
7.1 Introduction to DIGSI 5
SIPROTEC 5, Fault Recorder, Manual 223
C53000-G5040-C018-5, Edition 11.2017

Table of Contents

Other manuals for Siemens SIPROTEC 5

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 5 and is the answer not in the manual?

Siemens SIPROTEC 5 Specifications

General IconGeneral
SeriesSIPROTEC 5
Communication ProtocolsIEC 61850, DNP3, Modbus
CybersecurityRole-based access control, secure communication
Modular DesignYes
Hardware RedundancyOptional
Operating Temperature-25°C to +70°C
Digital InputsConfigurable, number depends on I/O modules
Digital OutputsConfigurable, number depends on I/O modules
Analog InputsConfigurable, number depends on I/O modules
Current Transformer InputsConfigurable, number depends on I/O modules
Voltage Transformer InputsConfigurable, number depends on I/O modules
Time SynchronizationIRIG-B, SNTP, PTP
Protection FunctionsOvercurrent, Differential, Distance, Over/Under Voltage, Frequency
Housing19-inch Rack Mount
DimensionsDepends on module configuration
WeightDepends on module configuration
Voltage Input24V DC, 48V DC, 110V DC, 125V DC, 220V DC, 250V DC

Related product manuals