DS92 (device messages)
Byte Message bit Error
category
DP error
no.
Comments
19
6
Reserved=0
19
7
Reserved=0
Configuration status:
20
0
Reserved=0
20
1
Reserved=0
20
2
Reserved=0
20
3
Reserved=0
20
4
Reserved=0
20
5
Reserved=0
20
6
Reserved=0
20
7
Reserved=0
21
0
Configuration missing SW The system does not contain a valid
configuration.
21
1
Configuration not released The configuration has not been released
or the release has been canceled.
21
2
Configuration released The configuration has been released.
21
3
Reserved=0
21
4
Release denied due to incorrect
configuration CRC
SF F24, F16 Incorrect configuration CRC, or other
incorrect entries (e.g. no time stamp,
name or description of company).
21
5
Release denied, already released The configuration cannot be released
because it has already been released.
21
6
Release canceled The release of a configuration has been
canceled.
21
7
Release canceled due to incorrect
configuration release CRC
SF F24, F16 The configuration release has been
canceled because the configuration
contains errors.
22
0
Max. number of elements exceeded SF F24, F8 The max. no. of system elements has
been exceeded.
22
1
Max. size of memory exceeded SF F24, F8 The max. size of the system memory has
been exceeded.
22
2
Program cycle time exceeded SF F24, F8 The set cycle time has been exceeded.
22
3
Reserved=0
22
4
TARGET=ACTUAL configuration The system configuration matches the
target configuration
22
5
TARGET≠ACTUAL configuration SF F24, F27 The system configuration does not match
the target configuration (e.g. modules
swapped)
22
6
TARGET≠ACTUAL slot
configuration
SF F24, F27 The system configuration does not match
the target configuration (e.g. different
number of modules)
22
7
Reserved=0
23
0
Reserved=0