Mounting / connection
4.2 Connection
M200D PROFIBUS/PROFINET
Manual, 08/2014, A5E01577426A/RS-AA/004
113
Requirements
The communication module is mounted on the motor starter module as shown in Chapter
Installing the communication module (Page 99)
You have set the PROFIBUS DP address on the DIP switch according to your
configuration. Further information: Setting the PROFIBUS DP address and terminating
resistor (Page 100)
Required tools
Screwdriver, (PZ 2; 2 Nm)
Stripping tool for wiring the M12 and 7/8" cable connectors, if you are fabricating your
own cables.
Required accessories
Prefabricated cable with M12 and 7/8" cable connectors The cables are available in
different lengths.
If you are fabricating your own cable:
M12: 2-core, shielded bus cable, and b-coded M12 cable connectors
7/8": 4-core cable with 7/8" cable connectors
Pin assignment of the M12 and 7/8" cable connectors
PROFIBUS connection (M12)
Coding (M12 B-coded)
Pin (infeed)
Socket (routing)
Pin
Assignment
M12-B
1 Power supply plus (5 V)
2 Data line A
3 Data reference potential (0 V)
4 Data line B
5 Functional ground (FE)
Note
The voltage must not be looped through to the next plug connector using a cable.
Note
The functional ground is to be connected via the M12 thread (because it has a larger surface
area than terminal 5).