Technical data
8.7 Switching frequency
M200D PROFIBUS/PROFINET
Manual, 08/2014, A5E01577426A/RS-AA/004
179
Switching cycles/hour for 3RK1395-6LS71-.AD.(1.5 A to 12 A)
e
1)
2)
1)
2)
1)
2)
1)
2)
1)
2)
1)
2)
ED=30 %, Start 4 x I
e
/ 1 s 250 340 250 250 210 210 250 290 210 210 170 170
ED=70 %, Start 4 x I
e
/ 1 s 150 290 150 200 150 160 150 240 150 170 125 125
ED=30 %, Start 4 x I
e
/ 2 s 120 170 120 120 105 105 120 145 105 105 88 88
ED=70 %, Start 4 x I
e
/ 2 s 70 140 70 100 70 80 70 120 70 82 63 63
ED=30 %, Start 4 x I
e
/ 2 s 120 170 120 120 105 105 120 145 105 105 88 88
ED=70 %, Start 4 x I
e
/ 2 s 70 140 70 100 70 80 70 120 70 82 63 63
ED=30 %, Start 4 x I
e
/ 4 s 60 85 60 60 53 53 60 72 53 53 44 44
ED=70 %, Start 4 x I
e
/ 4 s 38 72 38 50 38 38 38 60 38 41 31 31
ED=30 %, Start 4 x I
e
/ 3 s 80 115 80 85 70 70 80 97 71 71 58 58
ED=70 %, Start 4 x I
e
/ 3 s 50 95 50 65 50 52 50 80 50 55 42 42
ED=30 %, Start 4 x I
e
/ 6 s 40 57 40 42 35 35 40 48 35 35 29 29
ED=70 %, Start 4 x I
e
/ 6 s 26 48 26 33 26 26 25 40 25 27 21 21
ED=30 %, Start 4 x I
e
/ 4 s 60 85 60 60 53 53 60 72 53 53 44 44
ED=70 %, Start 4 x I
e
/ 4 s 38 72 38 50 38 38 38 60 38 41 31 31
ED=30 %, Start 4 x I
e
/ 8 s 30 42 30 30 26 26 30 36 26 26 22 22
ED=70 %, Start 4 x I
e
/ 8 s 18 36 18 25 18 18 19 30 19 20 15 15
1)
Duty cycle current rms value = 1.15 x I
e
→ motor protection
2)
Duty cycle limit for motor starter. The motor should be protected against overload here by means of a thermistor.