Technical data
8.7 Switching frequency
M200D PROFIBUS/PROFINET
180 Manual, 08/2014, A5E01577426A/RS-AA/004
Switching cycles/hour for 3RK1395-6LS71-.AD.(1.5 A to 12 A)
e
1)
2)
1)
2)
1)
2)
1)
2)
1)
2)
1)
2)
ED=30 %, Start 4 x I
e
/ 1 s 215 215 155 155 125 125 175 175 125 125 120 120
ED=70 %, Start 4 x I
e
/ 1 s 150 150 100 100 70 70 125 125 70 70 70 70
ED=30 %, Start 4 x I
e
/ 2 s 107 107 77 77 63 63 88 88 63 63 60 60
ED=70 %, Start 4 x I
e
/ 2 s 70 80 50 50 35 35 62 62 36 36 33 33
ED=30 %, Start 4 x I
e
/ 2 s 107 107 77 77 63 63 88 88 63 63 60 60
ED=70 %, Start 4 x I
e
/ 2 s 70 80 50 50 35 35 62 62 36 36 33 33
ED=30 %, Start 4 x I
e
/ 4 s 54 54 38 38 312 31 44 44 31 31 31 31
ED=70 %, Start 4 x I
e
/ 4 s 38 40 25 25 18 18 31 31 18 18 18 18
ED=30 %, Start 4 x I
e
/ 3 s 72 72 52 52 42 42 59 59 42 42 40 40
ED=70 %, Start 4 x I
e
/ 3 s 50 54 34 34 24 24 41 41 24 24 24 24
ED=30 %, Start 4 x I
e
/ 6 s 36 36 26 26 21 21 29 29 21 21 20 20
ED=70 %, Start 4 x I
e
/ 6 s 25 27 17 17 12 12 20 20 12 12 12 12
ED=30 %, Start 4 x I
e
/ 4 s 54 54 38 38 31 31 44 44 31 31 31 31
ED=70 %, Start 4 x I
e
/ 4 s 38 40 25 25 18 18 31 31 18 18 18 18
ED=30 %, Start 4 x I
e
/ 8 s 27 27 19 19 15 15 22 22 15 15 15 15
ED=70 %, Start 4 x I
e
/ 8 s 18 20 12 12 9 9 15 15 9 9 9 9
1)
Duty cycle current rms value = 1.15 x I
e
→ motor protection
2)
Duty cycle limit for motor starter. The motor should be protected against overload here by means of a thermistor.