Appendix
A.1 Data formats and data sets
M200D PROFIBUS/PROFINET
210 Manual, 08/2014, A5E01577426A/RS-AA/004
9 24.4 ... 6 Temperature sensor [0] Deactivated
[1] Thermoclick
[2] PTC Typ A
— [0] All starters
12 24.7 Temperature sensor
monitoring
[0] No
[1] Yes
— [1] All starters
15 28.0 ... 7 Lower current limit [6 ... 32] 18,75 ... 100 %
[0] deactivated
3.125 % 18.75 % All starters
16 29.0 ... 7 Upper current limit [16 ... 128] 50 % ... 150, 400 %
[0] deactivated
3.125 % 112.5 % All starters
17 30.0 ... 7 Blocking current 150 % .... 1000 %
With sDS.., sRS…:
150 % ... 800 %
50 % 800 % All starters
18 32.0 ... 3 Blocking time 1 s to 5 s 0.5 s 1 s All starters
114 32.4 ... 5 Response to switching
element supply voltage
cut-off
[0] Group fault
[1] Group fault only with ON
command
[2] Group warning
— [0] All starters
14 32.6 Response to current
limit violation
[0] Warning
[1] Trip
— [0] All starters
19 32.7 Response to residual
current detection
[0] Warning
[1] Trip
— [1] All starters
139 33.0 ... 1 Response to circuit
breaker OFF
[0] Group fault
[1] Group fault only with ON
command
[2] Group warning
— [0] All starters
21 34.0 ... 2 Asymmetry limit 30 % ... 60 %
[0] deactivated
10 % 30 % All starters
20 34.6 Response to asymmetry [0] Warning
[1] Trip
— [1] All starters
37 36.0 ... 7 Lock-out time 0 s to 60 s
Note:
Lock-out time = 0 means
a min. time of approx. 150 ms
for safety reasons!
1 s 0 s .RS..
190 37.0 ... 7 Input signal extension 0 ms to 200 ms 10 ms 0 ms All starters
24 38.0 ... 2 Input signal delay 10 ms to 80 ms 10 ms 10 ms All starters
25 38.4 Input 1 – level [0] NC contact
[1] NO contact
— [1] All starters
27 38.5 Input 2 – level [0] NC contact
[1] NO contact
— [1]
29 38.6 Input 3 – level [0] NC contact
[1] NO contact
— [1]
31 38.7 Input 4 – level [0] NC contact
[1] NO contact
— [1]