Appendix
A.1 Data formats and data sets
M200D PROFIBUS/PROFINET
Manual, 08/2014, A5E01577426A/RS-AA/004
211
Object
No.
Byte.Bit
Parameters / content
Range of values
Increment
Default
setting
Relevant for
26 39.0 ... 3 Input 1 action
NO contact/NC contact
NO contact/NC contact
NO contact/NC contact
NO contact/NC contact
NO contact/NC contact
NO contact/NC contact
NO contact
NO contact
NO contact
NO contact/NC contact
NO contact
NO contact
[0] No action
[1] Tripping without restart
[2] Tripping with restart
[3] Trip end position CW
[4] Trip end position CCW
[5] Group warning
[6] Manual local mode
[7] Emergency start
[8] Motor CW
[9] Motor CCW (on RS only)
[11] Quick stop
[12] Trip reset
[13] Cold start
[0] All starters
28 39.4 ... 7 Input 2 action
NO contact/NC contact
NO contact/NC contact
NO contact/NC contact
NO contact/NC contact
NO contact/NC contact
NO contact/NC contact
NO contact
NO contact
NO contact
NO contact/NC contact
NO contact
NO contact
[0] No action
[1] Tripping without restart
[2] Tripping with restart
[3] Trip end position CW
[4] Trip end position CCW
[5] Group warning
[6] Manual local mode
[7] Emergency start
[8] Motor CW
[9] Motor CCW (on RS only)
[11] Quick stop
[12] Trip reset
[13] Cold start
[0] All starters
30 40.0 ... 3 Input 3 action
NO contact/NC contact
NO contact/NC contact
NO contact/NC contact
NO contact/NC contact
NO contact/NC contact
NO contact/NC contact
NO contact
NO contact
NO contact
NO contact/NC contact
NO contact
NO contact
[0] No action
[1] Tripping without restart
[2] Tripping with restart
[3] Trip end position CW
[4] Trip end position CCW
[5] Group warning
[6] Manual local mode
[7] Emergency start
[8] Motor CW
[9] Motor CCW (on RS only)
[11] Quick stop
[12] Trip reset
[13] Cold start
[0] All starters
32 40.4 ... 7 Input 4 action
NO contact/NC contact
NO contact/NC contact
NO contact/NC contact
NO contact/NC contact
NO contact/NC contact
NO contact/NC contact
NO contact
NO contact
NO contact
NO contact/NC contact
NO contact
NO contact
[0] No action
[1] Tripping without restart
[2] Tripping with restart
[3] Trip end position CW
[4] Trip end position CCW
[5] Group warning
[6] Manual local mode
[7] Emergency start
[8] Motor CW
[9] Motor CCW (on RS only)
[11] Quick stop
[12] Trip reset
[13] Cold start
[0] All starters

Table of Contents