Appendix
A.1 Data formats and data sets
M200D PROFIBUS/PROFINET
Manual, 08/2014, A5E01577426A/RS-AA/004
213
Object
No.
Byte.Bit
Parameters / content
Range of values
Increment
Default
setting
Relevant for
163 96 Output 1 action [00]: No action
[01]: Control source PIO DO 1.0
[02]: Control source PIO DO 1.1
[03]: Control source PIO DO 0.2
[06]: Control source input 1
[07]: Control source input 2
[08]: Control source input 3
[09]: Control source input 4
[10]: Run-up
[11]: Operation/shunting
[12]: Coasting down
[13]: On time motor (RUN)
[14]: Control command motor
(ON)
[17]: Brake output
[18]: Device ON
[30]: Group prewarning
[31]: Group warning
[32]: Group fault
[33]: Bus error
[34]: Device error
[35]: Maintenance required
[36]: Maintenance requested
[38]: Ready for motor ON
[01] All starters
All starters
All starters
All starters
All starters
All starters
All starters
All starters
sDSS../sRSS..
sDSS../sRSS..
sDSS../sRSS..
All starters
All starters
With BO only
All starters
All starters
All starters
All starters
All starters
All starters
All starters
All starters
All starters
164 97 Output 2 action [00]: No action
[01]: Control source PIO DO 1.0
[02]: Control source PIO DO 1.1
[03]: …[38]: See byte 96
[02] All starters
All starters
All starters
230 137.0 ... 3 Connector monitoring [0]: Deactivated
[1]: Line side
[0] All starters
231 137.4 ... 7 Response when
connector removed
[0]: Group fault
[1]: Group fault only after ON
command
[2]: Group warning
[0] All starters
1)
BO: Brake output