Functions
3.7 System monitoring
M200D PROFIBUS/PROFINET
50 Manual, 08/2014, A5E01577426A/RS-AA/004
Blocking protection principle in run-up phase:
The figure below shows the principle of blocking protection during the run-up phase, that is,
the interaction of blocking current and blocking time:
Figure 3-6 Blocking protection principle
Blocking protection principle after run-up
After run-up, blocking protection behaves as follows during continuous operation:
The blocking time is reduced to 1 s regardless of the parameterized value.
The blocking current is limited to a maximum of 400%.
With a parameterized blocking current < 400%, the parameter value is valid.
When the blocking protection responds, the motor starter itself generates a trip command.
The messages "Tripping due to motor blocking" and "Group fault" are generated.
The maximum pointer "Number of motor overload trips" is incremented by 1.