Functions
3.7 System monitoring
M200D PROFIBUS/PROFINET
Manual, 08/2014, A5E01577426A/RS-AA/004
51
Response to residual current detection Trip
• Warning
• Trip
Response to current limit violation Warning
• Warning
• Trip
Lower current limit 18,75 %
• 18.75 to 100% of I
e
• 0% (= deactivated)
Increment: 3,125 %
Upper current limit 112,5 %
• 50 to 400% of I
e
• 0% (= deactivated)
Increment: 3,125 %
Blocking current 800 %
• 150 to 1000% of I
e
• 150 ... 800% of I
e
(sDSSte, sRSSte)
Increment: 50 %
Blocking time 1 s 1 to 5 s
Increment: 0.5 s
I
e
upper limit violation -
I
e
lower limit violation Dependent on parameterization
I
e
limit tripping Trip (limit violation pending)
Residual current detected Dependent on parameterization
Residual current tripping Trip (residual current detection)
Tripping due to motor blocking Trip (blocking protection)