SITRANS LUT400
190 Operating Instructions, 07/2019, A5E33329501-AC
Peak 1 End Time (2.7.2.2.4.)
Sets the end time of the high energy cost period 1.
Values
Range: 00:00 to 23:59
Format: HH:MM (24 hour format, for example: for 5:30pm, set parameter to 17:30)
Default: 00:00
Used in conjunction with Peak 1 Start Time (2.7.2.2.3.) (Page 189) to define the high cost
period.
For instructions on how to edit parameters with a string editor, see Using the string editor in
Date and Time (2.14.) (Page 226).
Peak 2 Start Time (2.7.2.2.5.)
Sets the start time of the high energy cost period 2.
Values
Range: 00:00 to 23:59
Format: HH:MM (24 hour format, for example: for 5:30pm, set parameter to
17:30
)
Default: 00:00
Used in conjunction with Peak 2 End Time (2.7.2.2.6.) (Page 190) to define the high cost
period.
Peak 2 End Time (2.7.2.2.6.)
Sets the end time of the high energy cost period 2.
Values
Range: 00:00 to 23:59
Format: HH:MM (24 hour format, for example: for 5:30pm, set parameter to 17:30)
Default: 00:00
Used in conjunction with Peak 2 Start Time (2.7.2.2.5.) (Page 190) to define the high cost
period.
Peak 3 Start Time (2.7.2.2.7.)
Sets the start time of the high energy cost period 3.
Values
Range: 00:00 to 23:59
Format: HH:MM (24 hour format, for example: for 5:30pm, set parameter to 17:30)
Default: 00:00
Used in conjunction with Peak 3 End Time (2.7.2.2.8.) (Page 191) to define the high cost
period.