D300529 0115 - BL67 I/O modules
6-53
BL67-4AI-V/I, voltage-/current measurement
Extended range - value representation
16-bit-representation
-10 … 10 V bipolar Diagnostics dec. hex.
voltage value U
M
= (dec. value × 3,617 × 10
-4
) V
≥ 11.851490 V
overflow
32767 7FFF
≥ 11.758773 V
at ↑ DIA Measured value
out of range ON
32512 7F00
11.7584 V
over-
steering
32511 7EFF
≤ 11.603010 V
at ↓ DIA Measured value
out of range OFF
32080 7D50
10.000305 V 27649 6C01
10.000000 V
nominal range
27648 6C00
………
5.0000 V 13824 3600
………
0.0003617 V 1 0001
0.000000 V 0 0000
-0.0003617 V -1 FFFF
………
-5.000000 V -13824 CA00
………
-10.000000V -27648 9400
-10.000362 V
under-
steering
-27649 93FF
≥ -11,60301 V
at ↑ DIA Measured value
out of range OFF
-32080 82B0
-11.758897 V -32511 8100
-11.759259 V
underflow
at ↓ DIA Measured value
out of range ON
-32512 80FF
≤ -11.851851 V -32768 8000