Analog input modules
D300529 0115 - BL67 I/O modules6-52
0 … 20 mA unipolar Diagnostics dec. hex.
current value U
M
= (dec. value/16 × 4,884 × 10
-3
) mA
> 20.2000 mA
at DIA Measured value out
of range ON
4095 × 16 FFF×
20.1000 mA
at DIA Measured value
out of range OFF
4095 × 16 FFF×
20.0000 mA
nominal range
4095 × 16 FFF×
19.9951 mA 4094 × 16 FFE×
……
10.0024 mA 2048 × 16 800×
……
0.00488 mA 1 × 16 001×
0,0000 mA 0 000×
4 … 20 mA unipolar Diagnostics dec. hex.
current value
M
= (dec. value/16 × 3,907 × 10
-3
) + 4) mA
> 20.2000 mA
at DIA Measured value
out of range ON
4095 × 16 FFF×
20.1000 mA
at DIA Measured value
out of range OFF
4095 × 16 FFF×
20.0000 mA
nominal range
4095 × 16 FFF×
19.9961 mA 4094 × 16 FFE×
……
12.0020 mA 2048 × 16 800×
……
4.0039 mA 1 × 16 001×
4.0000 mA 0 000×
3,7000 mA
at DIA Measured value
out of range OFF
0000×
< 3,6000 mA
at DIA Measured value out
of range ON
0000×
3,0000 mA
at DIA Wire break OFF 0 000×
< 2,9000 mA
at DIA Wire break ON 0 000×