EasyManua.ls Logo

turck BL67 - Page 139

turck BL67
507 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
D300529 0115 - BL67 I/O modules
6-51
BL67-4AI-V/I, voltage-/current measurement
12-bit-representation (left-justified)
NOTE
If the measurement value representation is parameterized as "12bit left-justified" the diag-
nostic data will be transferred with the process data bits 0 to 3 of the respective channel.
-10 … 10 V bipolar Diagnostics dec. hex.
voltag
e value U
M
= (dec. value/16 × 4,885 × 10
-3
) V
> 10.1000 V
at DIA Measured value out
of range ON
2047 × 16 7FFF
10.0500 V
at DIA Measured value
out of range OFF
2047 × 16 7FFF
10.0000 V
nominal range
2047 × 16 7FFF
9.9951 V 2046 × 16 7FE×
……
5.00244 V 1024 × 16 400×
……
0.00488 V 1 × 16 001×
0.000000 V 0 000×
-0.000488 V -1 × 16 FFF×
……
-5.0000 V -1024 × 16 C00×
……
-9.99511 V -2047 × 16 801×
-10.0000 V -2048 × 16 800×
-10,0500 V
at DIA Measured value
out of range OFF
-2048 × 16 800×
< -10,1000 V
at DIA Measured value
out of range ON
-2048 × 16 800×
0 … 10 V unipolar Diagnostics dec. hex.
voltage value U
M
= (dec. value/16 × 2,442 × 10
-3
) V
> 10.1000 V
at DIA Measured value
out of range ON
4095 × 16 FFF×
10.0500 V
at DIA Measured value
out of range OFF
4095 × 16 FFF×
10.0000 V
nominal range
4095 × 16 FFF×
9.9976 V 4094 × 16 FFE×
……
5.0012 V 2048 × 16 800×
……
0.00244 V 1 × 16 001×
0.0000 V 0 000×
-0,0500 V
at DIA Measured value
out of range OFF
0000×
< -0,1000 V
at DIA Measured value
out of range ON
0000×