D300529 0115 - BL67 I/O modules
6-55
BL67-4AI-V/I, voltage-/current measurement
0 … 20 mA bipolar Diagnostics dec. hex.
current value
M
= (dec. value × 7,234 × 10
-4
) mA
≥ 23.70298 mA
overflow
32767 7FFF
≥ 23.5185 mA
at ↑ DIA Measured value
out of range ON
32512 7F00
23.517795 mA
over-
steering
32511 7EFF
≤ 23.2060 mA
at ↓ DIA Measured value
out of range OFF
32080 7D50
20.000723 mA 27649 6C01
20.000000 mA
nominal range
27648 6C00
………
10.0000 mA 13824 3600
………
0.0007234 mA 1 0001
0.000000 mA 0 0000
4 … 20 mA bipolar Diagnostics dec. hex.
current value
M
= (dec. value × 5,787 × 10
-4
) mA
≥ 22.96238 mA
overflow
32767 7FFF
≥ 22.81481 mA
at ↑ DIA Measured value
out of range ON
32512 7F00
22.814236 mA
over-
steering
32511 7EFF
≤ 22.56482 mA
at ↓ DIA Measured value
out of range OFF
32080 7D50
20.000579 mA 27649 6C01
20.000000 mA
nominal range
27648 6C00
………
12.0000 mA 13824 3600
………
4.0005787 mA 1 0001
4.000000 mA 0 0000
3.999421 mA
under-
steering
-1 FFFF
≥ 1.30324 mA
at ↑ DIA Measured value
out of range OFF
-4672 EDC0
1.185185 -4864 ED00
≤ 1.184606 mA
underflow
at ↓ DIA Measured value
out of range ON
-4865 ECFF
≤ 0.0000 mA -6912 E500