Analog input modules
D300529 0115 - BL67 I/O modules6-56
12-bit-representation (left-justified)
The representation of the 12 bit values corresponds to that of the 16 bit values. Only bits 0 to 3 are set
to "0". Diagnostic data are not mapped to the process data.
-10 … 10 V bipolar Diagnostics dec. hex.
voltage value U
M
= (dec. value/16 × 5,787 × 10
-3
) V
11.8460 V
overflow
2047 × 16 7FF0
11.7592 V
at DIA Measured value
out of range ON
2032 × 16 7F00
11.7535 V
over-
steering
2031 × 16 7EF0
11.6030 V
at DIA Measured value
out of range OFF
2005 × 16 7D50
10.0058 V 1729 × 16 6C10
10.000000 V
nominal range
1728 × 16 6C00
……
5.0000 V 864 × 16 3600
……
0.000578 V 1 × 16 0010
0.000000 V 0 0000
-0.000578 V -1 × 16 FFF0
……
-5.000000 V -864 × 16 CA00
……
-10.000000V -1728 × 16 9400
-10.0058 V
under-
steering
-1729 × 16 93F0
-11,6030 V
at DIA Measured value
out of range OFF
-2005 × 16 82B0
-11.7592 V -2032 × 16 8100
-11.7650 V
underflow
at DIA Measured value
out of range ON
-2033 × 16 80F0
-11.8518 V -2048 × 16 8000