D300529 0115 - BL67 I/O modules
6-57
BL67-4AI-V/I, voltage-/current measurement
0 … 10 V bipolar Diagnostics dec. hex.
voltage value U
M
= (dec. value/16 × 5,787 × 10
-3
) V
11.8460 V
overflow
2047 × 16 7FF0
11.7592 V
at DIA Measured value
out of range ON
2032 × 16 7F00
11.7535 V
over-
steering
2031 × 16 7EF0
11.6030 V
at DIA Measured value
out of range OFF
2005 × 16 7D50
10.0058 V 1729 × 16 6C10
10.000000 V
nominal range
1728 × 16 6C00
……
5.0000 V 864 × 16 3600
……
0.000578 V 1 × 16 0010
0.00000 V 0 0000
-0.050 V
underflow
at DIA
Overflow/underflow OFF
00000
< -0,100 V
at DIA
Overflow/underflow ON
00000