Analog input modules
D300529 0115 - BL67 I/O modules6-58
0 … 20 mA bipolar Diagnostics dec. hex.
current value
M
= (dec. value/16 × 0,01157) mA
23.6921 mA
overflow
2047 × 16 7FF0
23.5185 mA
at DIA Measured value
out of range ON
2032 × 16 7F00
23.5069 mA
over-
steering
2031 × 16 7EF0
23.2060 mA
at DIA Measured value
out of range OFF
2005 × 16 7D50
20.0116 mA 1729 × 16 6C10
20.000000 mA
nominal range
1728 × 16 6C00
……
10.0000 mA 864 × 16 3600
……
0.01157 mA 1 × 16 0010
0.0000 mA 0 0000
-0,1 mA
underflow
at DIA
Overflow/underflow OFF
00000
< -0,2 mA
at DIA
Overflow/underflow ON
00000
4 … 20 mA bipolar Diagnostics dec. hex.
current value
M
= (dec. value/16 × 9,259 × 10
-3
) + 4) mA
22.9537 mA
overflow
2047 × 16 7FF0
22.8148 mA
at DIA Measured value
out of range ON
2032 × 16 7F00
22.8056 mA
over-
steering
2031 × 16 7EF0
22.5648 mA
at DIA Measured value
out of range OFF
2005 × 16 7D50
20.0093 mA 1729 × 16 6C10
20.000000 mA
nominal range
1728 × 16 6C00
……
12.0000 mA 864 × 16 3600
……
4.00925 mA 1 × 16 0010
40000 mA 0 0000
3,9907 mA
under-
steering
-1 × 16 FFF0
1.2963 mA
at DIA Measured value
out of range OFF
-292 × 16 EDC0
1.1851 mA -304 × 16 ED00
1.1759 mA
underflow
at DIA Measured value
out of range ON
-305 × 16 ECF0
0.000 mA -432 × 16 E500