Analog input modules
D300529 0115 - BL67 I/O modules6-64
4 … 20 mA unipolar Diagnostics dec. hex.
current value
M
= (dec. value/16 × 0,001) mA
≥ 22,000 mA
overflow
at ↑ DIA Overflow/under-
flow ON
22000 55F×
≤ 21.984 mA
at ↓ DIA Overflow/under-
flow OFF
21984 55E×
≥ 21.008 mA
over-
steering
at ↑ DIA Measured value out
of range ON
21008 521×
≤ 20.992 mA 20496 5010
≤ 20.496 mA
at ↓ DIA Measured value
out of range OFF
20.016 mA 20016 4E3×
20,000 mA
nominal range
20000 4E2×
………
12.000 mA 12000 2EE×
………
4.016 mA 4016 0FB×
4.000 mA 4000 0FA×
3.984 mA
under-
steering
3984 0F9×
≥ 3.792 mA
at ↑ DIA Measured value
out of range OFF
3792 0ED×
< 3,600 mA
at ↓ DIA Measured value
out of range ON
3600 0E1×
3.584 mA
underflow
3584 0E0×
≥ 2,001 mA
at ↑ DIA Wire break OFF 2001 07D×
< 2,000 mA
at ↓ DIA Wire break ON 2000 07D×
0.000 mA 0000 000×