D300529 0115 - BL67 I/O modules
6-63
BL67-4AI-V/I, voltage-/current measurement
0 … 10 V bipolar Diagnostics dec. hex.
voltage value U
M
= (dec. value × 0,001) V
≥ 11,008 V
overflow
11008 2B0×
≤ 10.992 V 10992 2AF×
10.512 V
at ↑ DIA Measured value out
of range ON
10512 291×
≥ 10.496 V
over-
steering
10496 290×
≤ 10.256 V
at ↓ DIA Measured value
out of range OFF
10256 281×
10.016 V 10016 272×
10.000 V
nominal range
10000 271×
…
4.992 V 4992 138×
………
0.016 V 16 001×
≤ 0.0000 V 0 000×
≥ -0.05 V
underflow
at ↑ DIA Measured value out
of range OFF
0000×
< -0,1 V
at ↓ DIA Measured value
out of range ON
0000×
0 … 20 mA unipolar Diagnostics dec. hex.
current value
M
= (dec. value/16 × 0,001) mA
≥ 22,000 mA
overflow
at ↑ DIA
Overflow/underflow ON
22000 55F×
≤ 21.984 mA
at ↓ DIA
Overflow/underflow OFF
21984 55E×
21.024 mA 21024 522×
≥ 21.008 mA
over-
steering
at ↑ DIA Measured value
out of range ON
21008 521×
≤ 20.496 mA
at ↓ DIA Measured value
out of range OFF
20496 501×
20.016 mA 20016 4E3×
20,000 mA
nominal range
20000 4E2×
………
10.000 mA 10000 271×
………
0.016 mA 16 001×
0.0000 mA 0 000×