Loading...
Analog combi modules
D300529 0115 - BL67 I/O modules10-12
0 … 20 mA unipolar Diagnostics dec. hex.
current value
M
= (dec. value × 6,104 × 10
-4
) mA
> 20.2000 mA
at DIA Measured value out
of range
ON
32767 7FFF
20.1000 mA
at DIA Measured value out
of range
OFF
32767 7FFF
20.0000 mA
nominal range
32767 7FFF
19.9994 mA 32766 7FFE
……
10.0003 mA 16384 4000
……
0.0006104 mA 1 0001
0.0000 mA 0 0000
-0.1 mA
at DIA Measured value out
of range
OFF
00000
< -0,2 mA
at DIA Measured value out
of range
ON
00000
4 … 20 mA unipolar Diagnostics dec. hex.
current value
M
= (dec. value × 4,883 × 10
-4
) + 4) mA
> 20.2000 mA
at DIA Measured value out
of range
ON
32767 7FFF
20.1000 mA
at DIA Measured value out
of range
OFF
32767 7FFF
20.0000 mA
nominal range
32767 7FFF
19.9995 mA 32766 7FFE
……
12.00024 mA 16384 4000
……
4.0004883 mA 1 0001
4.0000 mA 0 0000
3,7000 mA
at DIA Measured value out
of range
OFF
00000
< 3.6000 mA
at DIA Measured value out
of range
ON
00000
3,0000 mA
at DIA Wire break OFF 0 0000
< 2.9000 mA
at DIA Wire break ON 0 0000

Table of Contents

Other manuals for turck BL67

Related product manuals