EasyManua.ls Logo

turck BL67 - Page 310

turck BL67
507 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Analog combi modules
D300529 0115 - BL67 I/O modules10-14
0 … 20 mA unipolar Diagnostics dec. hex.
current value U
M
= (dec. value/16 × 4,884 × 10
-3
) mA
> 20.2000 mA
at DIA Measured value out
of range
ON
4095 × 16 FFF×
20.1000 mA
at DIA Measured value out
of range
OFF
4095 × 16 FFF×
20.0000 mA
nominal range
4095 × 16 FFF×
19.9951 mA 4094 × 16 FFE×
……
10.0024 mA 2048 × 16 800×
……
0.00488 mA 1 × 16 001×
0,0000 mA 0 000×
-0.1 mA
under-
drive
at DIA Measured value out
of range
OFF
0000×
< -0,2 mA
at DIA Measured value out
of range
ON
0000×
4 … 20 mA unipolar Diagnostics dec. hex.
current value
M
= (dec. value/16 × 3,907 × 10
-3
) + 4) mA
> 20.2000 mA
at DIA Measured value out
of range
ON
4095 × 16 FFF×
20.1000 mA
at DIA Measured value out
of range
OFF
4095 × 16 FFF×
20.0000 mA
nominal range
4095 × 16 FFF×
19.9961 mA 4094 × 16 FFE×
……
12.0020 mA 2048 × 16 800×
……
4.0039 mA 1 × 16 001×
4.0000 mA 0 000×
3,7000 mA
at DIA Measured value out
of range
OFF
0000×
< 3,6000 mA
at DIA Measured value out
of range
ON
0000×
3,0000 mA
at DIA Wire break OFF 0 000×
< 2,9000 mA
at DIA Wire break ON 0 000×

Table of Contents

Other manuals for turck BL67

Related product manuals