Analog combi modules
D300529 0115 - BL67 I/O modules10-16
0 … 10 V bipolar Diagnostics dec. hex.
voltage value U
M
= (dec. value × 3,617 × 10
-4
) V
≥ 11.851 V
overflow
32767 7FFF
≥ 11.7588 V
at ↑ DIA Measured value out
of range
ON
32512 7F00
11.7584 V
under-
drive
32511 7EFF
≤ 11.603010 V
at ↓ DIA Measured value out
of range
OFF
32080 7D50
10.000305 V 27649 6C01
10.000000 V
nominal range
27648 6C00
………
5.0000 V 13824 3600
………
0.000361 V 1 0001
0.000000 V 0 0000
< 0,000000 V 0 0000
≥ -0,050 V
underflow
at ↑ DIA Overflow/underflow
OFF
00000
< -0,100 V
at ↓ DIA Overflow/underflow
ON
00000
0 … 20 mA bipolar Diagnostics dec. hex.
current value
M
= (dec. value × 7,234 × 10
-4
) mA
≥ 23.70298 mA
overflow
32767 7FFF
≥ 23.51852 mA
at ↑ DIA Measured value out
of range
ON
32512 7F00
23.517795 mA
over-
drive
32511 7EFF
≤ 23.2060 mA
at ↓ DIA Measured value out
of range
OFF
32080 7D50
20.000723 mA 27649 6C01
20.000000 mA
nominal range
27648 6C00
………
10.0000 mA 13824 3600
………
0.0007234 mA 1 0001
0.000000 mA 0 0000
≥ -0.1 mA
under-
flow
at ↑ DIA Overflow/underflow
OFF
0000×
< -0,2 mA
at ↓ DIA Overflow/underflow
ON
0000×