D300529 0115 - BL67 I/O modules
10-17
BL67-4AI4AO-VI, voltage/current
4 … 20 mA bipolar Diagnostics dec. hex.
current value
M
= (dec. value × 5,787 × 10
-4
) mA
≥ 22.96238 mA
overflow
32767 7FFF
≥ 22.81481 mA
at ↑ DIA Measured value out
of range
ON
32512 7F00
22.814236 mA
over-
drive
32511 7EFF
≤ 22.56482 mA
at ↓ DIA Measured value out
of range
OFF
32080 7D50
20.000579 mA 27649 6C01
20.000000 mA
nominal range
27648 6C00
………
12.0000 mA 13824 3600
………
4.0005787 mA 1 0001
4.000000 mA 0 0000
3.999421 mA
under-
drive
-1 FFFF
≥ 1.5567 mA
at ↑ DIA Measured value out
of range
OFF
-4222 EEBA
1.185185 -4864 ED00
≤ 1.184606 mA
underflow
at ↓ DIA Measured value out
of range
ON
-4865 ECFF
≤ 0.0000 mA -6912 E500