EasyManua.ls Logo

YASKAWA T1000A - Page 377

YASKAWA T1000A
517 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
B.3 Parameter Table
YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual 377
Parameter List
B
n C6: Carrier Frequency
C5-38
(279H)
Motor 2 Load Inertia Ratio
Sets the ratio between the motor 2 and machine inertia. This value is automatically set during
ASR or Inertia Auto-Tuning.
Default: 1.0
Min: 0.0
Max: 6000.0
151
<7> Default setting value is dependent on the motor code set to E5-01.
<24> Default setting value is dependent on the drive model set to o2-04 and the Drive Duty set to C6-01.
<25> Default setting is determined by the control mode for motor 2 (E3-01).
<29> The setting range is 1.00 to 300.0 in CLV, AOLV/PM, or CLV/PM.
<34> Default setting is determined by the control mode (A1-02).
No.(Addr.)
<1> Default setting value is dependent on the drive model (o2-04), the control mode (A1-02), and the Drive Duty (C6-01).
<5> Default setting value is dependent on parameter C6-02, Carrier Frequency Selection.
Name Description Setting Page
C6-01
(223H)
Drive Duty Selection
0: Heavy Duty (HD)
Overload Tolerance: 150% rated output current (HD) for 60 s
Carrier Frequency: 2 kHz (default)
1: Normal Duty (ND)
Overload Tolerance: 120% rated output current (ND) for 60 s
Carrier Frequency: 2 kHz, Swing PWM (default)
Default: 0
Min: 0
Max: 1
152
C6-02
(224H)
Carrier Frequency Selection
1: 2.0 kHz
2: 5.0 kHz (4.0 Hz)
3: 8.0 kHz (6.0 Hz)
4: 10.0 kHz (8.0 Hz)
5: 12.5 kHz (10.0 Hz)
6: 15.0 kHz (12.0 Hz)
F: User defined (determined by C6-03 through C6-05)
Note: The default setting is 2 when using a PM motor. In all other control modes, 1 for HD and
ND.
Default:
<1>
Min: 1
Max: F
152
C6-03
(225H)
Carrier Frequency Upper Limit
Note: C6-04 and C6-05 are available only in V/f and V/f w/PG control modes.
Determines the upper and lower limits for the carrier frequency.
In OLV, C6-03 determines the upper limit of the carrier frequency.
Default:
<5>
Min: 1.0 kHz
Max: 15.0 kHz
153
C6-04
(226H)
Carrier Frequency Lower Limit
Default:
<5>
Min: 1.0 kHz
Max: 15.0 kHz
153
C6-05
(227H)
Carrier Frequency Proportional
Gain
Default:
<5>
Min: 0
Max: 99
153
C6-06
(228H)
PWM Method
0: 2-phase/3-phase conversion
1: 2-phase modulation
2: 3-phase modulation
Default:
<5>
Min: 0
Max: 2
153
C6-09
(22BH)
Carrier Frequency during
Rotational Auto-Tuning
0: Carrier Frequency = 5 kHz
1: Setting value for C6-03
Default: 0
Min: 0
Max: 1
154
No.(Addr.) Name Description Setting Page
OLV/PM AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f OLV
All Modes
All Modes
All Modes
Carrier Frequency
E1-04
Max Output
Frequency
Output Frequency
× (C6-05) × K
Output
Frequency
C6-03
C6-04
OLV/PM AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f OLV
OLV/PM AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f OLV

Table of Contents