EasyManuals Logo

YOKOGAWA UT55A User Manual

YOKOGAWA UT55A
476 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #136 background imageLoading...
Page #136 background image
8-7
IM 05P01C31-01EN
Control Functions
8
n
Single-loopPositionProportionalControlFunctionBlockDiagram
Target setpoints 1 to 8
COM
Analog input
*1
LOCALREMOTE
SP ramp rate
SP limiter
PV input Remote input
DI16PV RSP
Feedforward input
AIN2
Input type
Input unit
Input range/scale
Analog input bias
Square root extraction
Analog input filter
Input type
Input unit
Input range/scale
Analog input bias
Square root extraction
Analog input filter
10-seg. linearizer approx./bias
Remote input filter
PV input bias
PV input filter
Ratio bias computation
Contact inputs
A.BS
A.FL
BS
FL
PMD An, Bn
10-seg. linearizer approx./bias
PMD An, Bn
PMD An, Bn
CNT ALG
UPR, DNR TMU
SPNO SP
RT RBS
R/L
RMS
SPH, SPL
RFL
A.SR A.LC
UNIT
IN
RH, RL SDP SH, SL
A.BS
A.FL
10-seg. linearizer approx./bias
A.SR A.LC
UNIT
IN
RH, RL SDP SH, SL
Equipped as standard
DI3DI2DI1
No function
is assigned
to DI3.
REMOTE (ON)/LOCAL (OFF)
switch
Control computation
Input type
Input unit
Input range/scale
Analog input bias
Square root extraction
Analog input filter
PMD An, Bn
A.BS
A.FL
10-seg. linearizer approx./bias
A.SR A.LC
UNIT
IN
RH, RL
SDP
SH, SL
Manual operation
Input error preset output
Preset output
AUTO (ON)/MAN (OFF) switch
STOP (ON)/RUN (OFF) switch
AUTO
When sensor
burnout
occurs
Normal
MAN
RUNSTOP
Output limiter
EPO
OH, OL
PO
S/R
Signal comparison
Feedback input
Direct/reverse signal
Valve position sliding
resistor or current
Motor-operated valve
Relay output
VALV
FBIN
M
Equipped as standard Equipped as standard Equipped as standard
Current
LPS
24 V loop
power supply
Current
OUT RET AL3AL2AL1
PMD
OU.H OU.L
An, Bn
Split computation
10-seg. linearizer approx./bias
RET.H
HYS
DB
PMD An, Bn
Split computation
10-seg. linearizer approx./bias
OUT retransmission output
O1RS
RET retransmission output
RTS
Alarm
A/M
In Estimating-type position proportional control, the limiter function
does not work on output operation.
The reverse-signal relay turns on when being limited by low limit.
The direct-signal relay turns on when being limited by high limit.
H relay
( key)
L relay
( key)
In Manual operation, the relay turns on while the
or key is pressed. Output limiter does not work.
Alarm 1
(PV high limit)
Alarm 2
(PV low limit)
Alarm 3
(PV high limit)
Terminal Parameter Function
Analog signal Contact signal Front panel key
Legend
PV display SP display
Input ladder calculation program (signal goes to the control computation as is when without ladder program). For ladder program, see the LL50A Parameter Setting Software User’s Manual.
Output ladder calculation program (signal goes to the output as is when without ladder program). For ladder program, see the LL50A Parameter Setting Software User’s Manual.
Filter
Gain, bias
FLG
FGN
FBI FBO
Position Proportional Computation Output cannot be calculated by ladder program.
Communication
*1: RS-485, Ethernet, PROFIBUS-DP,
DeviceNet, CC-Link
Universal input (E1-terminal area) can be used
when UT55A/UT52A optional suffix code /U1.
However, DI16 does not exist.
(For Detailed model)
Remote input can be used when UT55A/UT52A
optional suffix code /R1 or /RCH1.
(For Standard model)
Remote input can be used when UT55A suffix code:
Type 2 = 1, 2, 4, 5, or 7; UT52A suffix code: Type 2 =
1 or 2.
(For Detailed model)
Feedforward input can be used when
UT55A optional suffix code /A2.
(For Standard model)
Feedforward input can be used when
UT55A suffix code: Type 2 = 7.
(For Detailed model)
DI16 is equipped when UT55A/UT52A
optional suffix code /R1 or /RCH1.
(For Standard model)
DI16 is equipped when UT55A suffix
code: Type 2 = 1, 2, 4, 5, or 7; UT52A
suffix code: Type 2 = 1 or 2.
8.1SettingControlMode(CTLM)