10-30
IM 05P01C31-01EN
10.16.1 SettingValveOperationMode
Description
Position proportional control monitors the control output signals and the feedback signals
from the control valve and regulates to keep the valve opening and the control output
signal in agreement.
Position proportional control (output) operation mode has feedback type and estimating
type.
Setting Details
Parameter
symbol
Name
Display
level
Setting range Menusymbol
V.MOD
Valveadjusting
mode
STD
0:Valve
positionfeedbacktype
1:Valvepositionfeedbacktype
(moves to the estimating type if
a feedback input error or break
occurs.)
2:Valvepositionestimatingtype
OUT
10.16.2 AdjustingValvePositionAutomatically
Description
The fully-closed and fully-opened positions of a valve can be set automatically by the
feedback input signal from a valve.
The
followingdescribes
theprocedureofadjustingthevalvepositionautomatically.
(1) Verifythatthewiringsarecorrect.
(2) Set the operation mode to MAN.
(3) Settheautomaticvalvepositionadjustment(V.AT)toON.(V.ATblinksduringthe
automaticadjustment.)
(4) Whentheadjustmentiscompleted,V.ATreturnstoOFF.
Whentheadjustmentfails,VAT.EappearsonPVdisplay.
Setting Details
Parameter
symbol
Name
Display
level
Setting range Menusymbol
V.AT
Automatic
valve position
adjustment
EASY
OFF:Stopautomatic
adjustment
ON:Startautomaticadjustment
OUT
10.16AdjustingMotor-operatedValvePosition(PositionProportionalOutput)