OperationinParameterSettingDisplay
Setting Display
Parameter Setting Display
Operation Display > PARAMETER or PARA key for 3
seconds (to [MODE] Menu Display) > Righta
rrow key (to [SP]
Menu Display ) > SET/ENTER key (The setting parameter is
displayed.)
Press the Right arrow key until the [SP]Me
nu Display appears.
In the Setting Display for the target setpoint parameter,
pressing the Left or Right arrow keys changes the group. (The
group number is displayed on Group display.)
Setting Details
Parameter
symbol
Name
Display
level
Setting range Menusymbol
SP Target setpoint EASY
0.0to100.0%
ofPVinputrange
(EU) (Setting range: SPL to SPH)
SP
SPGR.
Number of SP
groups
STD 1 to 8 CTL
Note1: In Cascade control, the LP2 lamp is lit while the Loop-2 parameter is displayed.
Note2: If the SP limiter is set, the setting can be made within the range of the SP limiter.
Description
The controller has eight target setpoints (SP).
In Cascade control, both Loop1 and Loop 2 have eight target setpoints.
► SPlimiter:9.1SettingSPLimiter
► SELECTparameter:13.1.5RegisteringSELECTParameterDisplay(Upto10Displays)
6.2SettingTargetSetpoint