AlarmFunctions
11
11.6 SettingAlarmActionAccordingtoOperation
Mode
Description
The alarm action usually functions regardless of operation modes.
Setting the alarm mode allows the alarm action to be disabled in STOP or in STOP or
MAN mode.
Setting Details
Parameter
symbol
Name
Display
level
Setting range Menusymbol
AMD Alarm mode STD
0: Always active
1: Not active in STOP mode
2: Not active in STOP or MAN
mode
ALRM
Note1: In Cascade control, the LP2 lamp is lit while the Loop-2 parameter is displayed.