Target setpoints 1 to 8
COM
Aux. input
*1
LOCALREMOTE
SP ramp rate
SP limiter
DI16PV RSP
Input type
Input unit
Input range/scale
Analog input bias
Square root extraction
Analog input filter
Input type
Input unit
Input range/scale
Analog input bias
Square root extraction
Analog input filter
10-seg. linearizer approx./bias
Remote input filter
PV input bias
PV input filter
Ratio bias computation
A.BS
A.FL
BS
PV-hold function
FL
PMD An, Bn
10-seg. linearizer approx./bias
PMD An, Bn
10-seg. linearizer approx./bias
PMD An, Bn
CNT ALG
UPR, DNR TMU
SPNO SP
R/L
RMS
SPH, SPL
RFL
A.SR A.LC
UNIT
IN
RH, RL SDP SH, SL
A.BS
A.FL
A.SR A.LC
UNIT
IN
RH, RL SDP SH, SL
DI3DI2DI1
REMOTE (ON)/LOCAL (OFF) switch
AUTO (OFF)/PV hold, MAN (ON) switch
Control computation
Manual operation
Manual preset output
Input error preset output
Heating-side preset output
STOP (ON)/RUN (OFF) switchSTOP (ON)/RUN (OFF) switch
AUTO
When sensor
burnout occurs
Normal Normal
MAN
RUNSTOP
EPO
OH, OL OHc, OLc
Error preset output
When sensor
burnout occurs
EPO
PO
Cooling-side preset output
STOP
POc
S/R
MPON
Heating/cooling computation
Heating-side output limiter Cooling-side output limiter
RUN
Current or
voltage pulse
Relay Current or
voltage pulse
Relay
LPS
24 V loop
power supply
Current
OUT retransmission output OUT2 retransmission output
OT
O1RS O2RS
RET retransmission output
RTS
Heating-side
output
Heating-side
output
OUTOUT
Cooling-side
output
Cooling-side
output
OUT2 OUT2 RET AL3AL2AL1
Output terminal assignment
PMD
OU.H OU.L OU2.H OU2.L
An, Bn PMD An, Bn
Split computation
10-seg. linearizer approx./bias
Split computation
10-seg. linearizer approx./bias
RET.H RET.L
PMD An, Bn
Split computation
10-seg. linearizer approx./bias
Alarm
Equipped as standard Equipped as standard
A/M
AUTO (ON)/PV hold, MAN (OFF) switch
(Current when retransmission output) (Current when retransmission output)
No function
is assigned
to DI3.
PV input Remote input Contact inputs
Equipped as standard
* After the control output terminal is specified by the parameter OT,
other current output terminals can be used as retransmission output.
Terminal Parameter Function
Analog signal Contact signal Front panel key
Legend
Alarm 1
(PV high limit)
Alarm 2
( PV low limit)
Alarm 3
(PV high limit)
PV display
SP display
Output ladder calculation program (signal goes to the output as is when without ladder program). For ladder program, see the LL50A Parameter Setting Software User’s Manual.
Manual output is prioritized even if
sensor burnout occurs in MAN.
Input ladder calculation program (signal goes to the control computation as is when without ladder program). For ladder program, see the LL50A Parameter Setting Software User’s Manual.
Communication
*1: RS-485, Ethernet, PROFIBUS-DP,
DeviceNet, CC-Link
Universal input (E1-terminal area) can be used
when UT55A/UT52A optional suffix code /U1.
However, DI16 does not exist.
(For Detailed model)
Remote input can be used when UT55A/UT52A
optional suffix code /R1 or /RCH1.
(For Standard model)
Remote input can be used when UT55A suffix
code: Type 2 = 1, 2, 4, 5, or 7; UT52A suffix
code: Type 2 = 1 or 2.
(For Detailed model)
DI16 is equipped when UT55A/UT52A optional
suffix code /R1 or /RCH1.
(For Standard model)
DI16 is equipped when UT55A suffix code: Type
2 = 1, 2, 4, 5, or 7; UT52A suffix code: Type 2 =
1 or 2.