10-27
IM 05P01C31-01EN
Output(ControlandRetransmission)Functions
10.15SettingSplitComputationOutputFunction
Description
Split computation output is useful for the case where multiple (up to 3) operating
units for switching, for example, hot and cool water are linked for control. There are
two
characteristicsof
splitcomputations:V-modecharacteristicsandParallel-mode
characteristics. The current output range can be changed.
► Currentoutputrange:10.14ChangingCurrentOutputRange
V-modeCharacteristics
The following explains an example of letting OUT terminal and RET terminal present the
V-modecharacteristicsofsplitcomputations.
SettingExample
OUT terminal RET terminal
Control output type/Retransmission output type OT=00.02
(current) RTS=OUT1
Currentoutput100%segmentalpoint OU.H=100.0% RET.H=0.0%
Currentoutput0%
segmentalpoint OU.L=25.0% RET.L=75.0%
Current output range OU.A=4-20 RET.A=4-20
0 5025 75 100 %
%mA
Output before split computation
Output after computation
OUT current output
100% segmental point
OUT current output
0% segmental point
RET current output
100% segmental point
RET current output
0% segmental point
RET terminal
25
0
50
75
10020
4
3.8
12
8
16
OUT terminal
10