Page #268 background image
10-27
IM 05P01C31-01EN
Output(ControlandRetransmission)Functions
10.15SettingSplitComputationOutputFunction
Description
Split computation output is useful for the case where multiple (up to 3) operating
units for switching, for example, hot and cool water are linked for control. There are
two
characteristicsof
splitcomputations:V-modecharacteristicsandParallel-mode
characteristics. The current output range can be changed.
► Currentoutputrange:10.14ChangingCurrentOutputRange
V-modeCharacteristics
The following explains an example of letting OUT terminal and RET terminal present the
V-modecharacteristicsofsplitcomputations.
SettingExample
OUT terminal RET terminal
Control output type/Retransmission output type OT=00.02
(current) RTS=OUT1
Currentoutput100%segmentalpoint OU.H=100.0% RET.H=0.0%
Currentoutput0%
segmentalpoint OU.L=25.0% RET.L=75.0%
Current output range OU.A=4-20 RET.A=4-20
0 5025 75 100 %
%mA
Output before split computation
Output after computation
OUT current output
100% segmental point
OUT current output
0% segmental point
RET current output
100% segmental point
RET current output
0% segmental point
RET terminal
25
0
50
75
10020
4
3.8
12
8
16
OUT terminal
10