EasyManua.ls Logo

YOKOGAWA UT55A - Chapter 11: Alarm Functions; 11.1 Setting Alarm Type

YOKOGAWA UT55A
476 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
11-1
IM 05P01C31-01EN
AlarmFunctions
11
11.1 SettingAlarmType
Description
Thealarm-relatedparametersconsistoft
healarmtype(type,stand-byaction,energized/
de-energized,andlatchfunction),PVvelocityalarmtimesetpoint,alarmhysteresis,
alarm (On-/Off-) delay timer, and alarm setpoint.
In Cascade control, both of Loop 1 and Loop 2 have these parameters.
Alarm-relatedparameter Numberofsettings
Alarm type 8 (number of settings) x 2 (number of loops)
PVvelocityalarmtimesetpoint 8 (number of settings) x 2 (number of loops)
Alarm hysteresis 8 (number of settings) x 2 (number of loops)
Alarm (on-/off-) delay timer 8 (number of settings) x 2 (number of loops)
Alarm setpoint
8 (number of settings) x 8 (number of groups) x 2 (number of loops)
► Alarmhysteresis:11.3SettingHysteresistoAlarmOperation
► Alarmdelaytimer:11.4DelayingAlarmOutput(AlarmDelayTimer)
► Alarmsetpoint:6.5SettingAlarmSetpoint
Both of Loop-1 and Loop-2 have eight groups of alarms. The alarms are assigned to the
terminals for each control mode (parameter CTLM).
Factory default: Only four groups of alarm-related parameters are displayed.
► Terminalfunction:17.4.7ContactOutputWiring
Alarm output can be assigned to the unused control relay output or contact output.
► Controlrelayoutput:11.5SettingAlarmOutputtoControlRelayTerminal
► Contactoutput:12.2.1SettingFunctionofContactOutput
Energized/de-energizedofalarmoutputcanbechanged.
► Energized/de-energized:12.2.2ChangingContactTypeofContactOutput
To read the conditions of alarms, outputs, or latches via communication, see
Communication Interface User's Manual.
……
AL3AL2AL1
Alarm 1
(PV high limit)
* See “Appendix 1 Input and Output Table of Standard Model and Suffix Codes” for presence/absence of the terminals
DO11 to DO15, DO21 to DO25, and DO31 to DO35.
* OUT1 and OUT2 can be used for alarm output when the relay outputs are not used for control otuput.
* The above figure shows the case of single-loop control mode.
DO12DO11 DO15
……
DO22DO21 DO25
……
DO32DO31 DO35
Alarm conditions
Alarm conditions
Alarm conditions
Alarm conditions
Energized/de-energized
Energized/de-energized Energized/de-energized Energized/de-energized
…… ……
……
Alarm 2
(PV low limit)
Alarm 3
(PV high limit)
OUT2OUT1
Alarm conditions
Energized/de-energized
Alarm 4
(PV low limit)
No function
No function
No function Alarm 5 Alarm 8 No function
No function
No function
Alarm Function
Chapter11AlarmFunctions

Table of Contents

Related product manuals