Output(ControlandRetransmission)Functions
10
10.12SettingPresetOutputValue
10.12.3 SettingOutputValueWhenErrorOccurs(InputErrorPresetOutput)
Description
The0%controloutput,100%controloutput,orinputpresetoutputcanbeselectedand
output as input error preset output in the following conditions.
•
The input burnout occurs during operation in AUTO or CAS mode and RUN mode.
• The
ADC error occurs during operation in AUTO or CAS mode and RUN mode.
However, the manual output becomes the output when the input burnout occurs in MAN
mode and RUN mode.
Setting Details
Parameter
symbol
Name
Display
level
Setting range Menusymbol
EPO
Input error preset
output
STD
0: Preset output
1:0%output
2:
100%output
SYS