10-22
IM 05P01C31-01EN
Setting Details
Parameter
symbol
Name
Display
level
Setting range Menusymbol
MPON
Manual preset output
number selection
STD
OFF: Hold the control output
in AUTO mode (bumpless)
1: Use manual preset output 1
(output bump)
2: Use manual preset output 2
(output bump)
3: Use manual preset output 3
(output bump)
4: Use manual preset output 4
(output bump)
5: Use manual preset output 5
(output bump)
TUNE
MPO1to
MPO5
Manual preset output 1
to 5
STD -5.0to105.0%
Note1: In Cascade control, the LP2 lamp is lit while the Loop-2 parameter is displayed.
10.12SettingPresetOutputValue