6-36
IM 05P01C31-01EN
6.7.3 SwitchingbetweenSTOPandRUN
Setting Display
Operation Mode Setting Display
Operation Display > PARAMETER or PARA key for
3 seconds (to [MODE] Menu Display) > SET/ENTER key
(The operation mode is displayed.) > Down arrow key (The
operation mode is displayed.)
Factory default: The parameter S.R is not displayed because
STOP/RUN switch is assigned to the contact input.
To display the parameter, disable the STOP/RUN switch
assigned to the contact input.
► Switch by contact input: 12.1 Setting Contact Input Function
Setting Details
Parameter
symbol
Name
Display
level
Setting range Menusymbol
S.R STOP/RUN switch EASY
STOP: Stop mode
RUN: Run mode
MODE
Description
STOP/RUN switching can be performed by any of the following:
(1) Contact input (status or edge)
(2) Parameter
(3) Communication
(4) User function key
表表
表表
WhentheSTOP/RUNswitchissettothecontactinput(S/R≠0),switchbykeystrokeor
via communication is disabled. Disable the setting if the STOP/RUN switch parameter
(S/R) is assigned to the contact input.
When the contact input is OFF, and the setting is switched by parameter, communication,
or keystroke, the last switching operation is performed.
► Switchbycontactinput:12.1SettingContactInputFunction
► Switchbyuserfunctionkey:13.2AssigningFunctiontoUserFunctionKeyandA/Mkey
Switch Outputaction
RUN→STOP The control output bumps.
STOP→RUN The control output does not bump (bumpless).
Output
Control output
Preset output
RUN → STOP STOP → RUN
► Presetoutputvalue:10.12.1SettingOutputValueinSTOPMode(PresetOutput)
6.7SwitchingOperationModes