8-66
IM 05P01C31-01EN
n
PositionProportionalLoopControlwithPV-holdFunctionFunctionBlockDiagram
Target setpoints 1 to 8
COM
Aux. input
*1
LOCALREMOTE
SP ramp rate
SP limiter
DI16PV RSP
Input type
Input unit
Input range/scale
Analog input bias
Square root extraction
Analog input filter
Input type
Input unit
Input range/scale
Analog input bias
Square root extraction
Analog input filter
10-seg. linearizer approx./bias
Remote input filter
PV input bias
PV input filter
Ratio bias computation
A.BS
A.FL
BS
PV-hold function
FL
PMD An, Bn
10-seg. linearizer approx./bias
PMD An, Bn
10-seg. linearizer approx./bias
PMD An, Bn
CNT ALG
UPR, DNR TMU
SPNO SP
R/L
RMS
SPH, SPL
RFL
A.SR A.LC
UNIT
IN
RH, RL SDP SH, SL
A.BS
A.FL
A.SR A.LC
UNIT
IN
RH, RL SDP SH, SL
PMD An, Bn
A.BS
A.FL
A.SR A.LC
UNIT
IN
RH, RL
SDP
SH, SL
DI3DI2DI1
REMOTE (ON)/LOCAL (OFF) switch
AUTO (OFF)/PV holde, MAN (ON) switch
AUTO (ON)/PV holde, MAN (OFF) switch
Control computation
Manual operation
Input error preset output
Preset output
STOP (ON)/RUN (OFF) switch
AUTO
When sensor burnout occurs
Normal
MAN
RUNSTOP
Output limiter
EPO
OH, OL
PO
S/R
Signal comparison
Feedback input
Direct/reverse signal
Valve position sliding
resistor or current
Motor-operated valve
Relay output
VALV
FBIN
M
Equipped as standard Equipped as standard Equipped as standard
Current
LPS
24 V loop
power supply
Current
OUT RET AL3AL2AL1
PMD
OU.H OU.L
HYS
DB
An, Bn
Split computation
10-seg. linearizer approx./bias
RET.H RET.L
PMD An, Bn
Split computation
10-seg. linearizer approx./bias
OUT retransmission output
O1RS
RET retransmission output
RTS
Alarm
A/M
PV input Remote input Contact inputs
Equipped as standard
No function
is assigned
to DI3.
In Estimating-type position proportional control, the limiter function
does not work on output operation.
The reverse-signal relay turns on when being limited by low limit.
The direct-signal relay turns on when being limited by high limit.
In Manual operation, the relay turns on while the
or key is pressed. Output limiter does not work.
H relay
( key)
L relay
( key)
Alarm 1
(PV high limit)
Alarm 2
(PV low limit)
Alarm 3
(PV high limit)
Terminal Parameter Function
Analog signal Contact signal Front panel key
Legend
PV display
SP display
Output ladder calculation program (signal goes to the output as is when without ladder program). For ladder program, see the LL50A Parameter Setting Software User’s Manual.
Filter
Gain, bias
FLG
FGN
FBI FBO
Feedforward input
Input type
Input unit
Input range/scale
Analog input bias
Square root extraction
Analog input filter
10-seg. linearizer approx./bias
AIN2
Input ladder calculation program (signal goes to the control computation as is when without ladder program). For ladder program, see the LL50A Parameter Setting Software User’s Manual.
Position Proportional Computation Output cannot be calculated by ladder program.
Communication
*1: RS-485, Ethernet, PROFIBUS-DP,
DeviceNet, CC-Link
Universal input (E1-terminal area) can be used
when UT55A/UT52A optional suffix code /U1.
However, DI16 does not exist.
(For Detailed model)
Remote input can be used when UT55A/UT52A
optional suffix code /R1 or /RCH1.
(For Standard model)
Remote input can be used when UT55A suffix
code: Type 2 = 1, 2, 4, 5, or 7; UT52A suffix
code: Type 2 = 1 or 2.
(For Detailed model)
Feedforward input can be used when
UT55A optional suffix code /A2.
(For Standard model)
Feedforward input can be used when
UT55A suffix code: Type 2 = 7.
(For Detailed model)
DI16 is equipped when UT55A/UT52A
optional suffix code /R1 or /RCH1.
(For Standard model)
DI16 is equipped when UT55A suffix
code: Type 2 = 1, 2, 4, 5, or 7; UT52A
suffix code: Type 2 = 1 or 2.
8.1SettingControlMode(CTLM)