7-1
IM 05P01C31-01EN
Input(PV,Remote,andAuxiliaryAnalog)Functions
7
7.1 SettingFunctionsofPVInput,RemoteInput,
and Auxiliary Analog Input
7.1.1 SettingInputType,Unit,Range,Scale,andDecimalPointPosition
Description
ThefigurebelowdescribesthecaseofPVinput.Theremoteinput
andauxiliaryanalog
input can be set in the same way.
ExampleofT
emperatureInput
The figure below is an example of setting Type K thermocouple and a measurement
range of 0.0 to 800.0 ºC.
Minimum value of PV input range
Input type
-270.0°C
1370.0°C
RL = 0.0°C RH = 800.0°C
Maximum value of PV input range
Set a range to be
controlled.
PV input range
ExampleofVoltageandCurrentInputs
Thefigurebelowisanexampleofsetting2-4VDCandascaleof0.0to50.0m³/h.
Minimum value of PV input scale
1 V 5 V
(input signal)
SL = 0.0 m³/h SH = 50.0 m³/h
Maximum value of PV input scale
2 V 4 V
RL = 2.000
RL = 1.000
RH = 4.000
RH = 5.000
PV input scale
Input type
Set a range to be
controlled.
PV input range
Whenusing1-5VDCsignalasis,setRH=5.000V,RL=1.000V,SDP=1,andSH=
50.0,andSL=0.0.
Chapter7Input(PV,Remote,andAuxiliaryAnalog)Functions